DESCRIPTION
Features
Specifications
Shipping & Delivery

Fluke 353 True-RMS 2000A Clamp Meter

Versatile and rugged tools for applications with high currents

Confidently take reliable readings with the True-rms, Fluke 355 and 353 digital clamp meters; the tools of choice for high current clamp-on amp meter measurement up to 2000 A. The extra-wide jaw easily clamps around large conductors, typically found in high-current applications. The extra rugged design and CAT IV 600 V, CAT III 1000 V ratings add an extra element of user protection when taking high-powered measurements.

Accurate peak measurements can be taken using the in-rush current mode, ideal for motors and inductive loads. The 355 also measures voltage and resistance, making this an ideal clamp meter for utilities, electrical contractors and industrial service technicians.

 includes

  • 353 clamp meter
  • C43 Soft carrying case
  • 6 AA batteries
  • User manual
  • 3 year warranty

Discover the Fluke 353 True-RMS 2000A Clamp Meter at Mektronics Australia – your trusted source for quality tools and equipment!

  • Reliably handle a wide range of high-current applications with 2000 A ac + dc true-rms, 1400 A ac, and 2000 A dc
  • The large 58 mm (2.3 in) jaw capacity is suitable for large or multiple conductors
  • CAT IV 600 V, CAT III 1000 V rating for added user protection
  • In-rush current measurement captures ‘power-on’ surge current with accuracy and repeatability
  • High voltage measurement of 1000 V ac + dc true-rms, 600 V ac, and 1000 V dc allows the user to perform multiple tests with only one tool (355 only)
  • Resistance to 400K ohms coupled with a continuity beeper provide the convenience of a multimeter in a clamp meter. (355 only)
  • Accurately measure frequency up to 1 kHz for optimum troubleshooting
  • Quickly analyze readings using the MIN, MAX, and AVG functions
  • A large backlit display allows for easy visibility in low-lit areas
  • Use the display hold feature to capture readings even when the display cannot be viewed
  • Use the low-pass filter to smooth out noisy loads and stabilize readings
Electrical Specifications
Current measurement DC and AC 10 Hz to 100 Hz Range 40 A / 400 A / 2000 A / 1400 AC RMS
Resolution 10 mA / 100 mA / 1 A
Accuracy A: 1.5% rdg + 15 digits
A: 1.5% rdg + 5 digits
Trigger level for Inrush 0.50 A / 5.0 A / 5 A
Trigger level for Hz filter OFF 2.50 A / 2.5 A / 8 A
Trigger level for Hz filter ON 0.50 A / 2.5 A / 8 A
Crest Factor (50/60 Hz) Range 40 A / 400 A / 2000 A / 1400 AC RMS
Crest Factor1 2 @ 33 A, 2.4 @ 27 A
2 @ 330 A, 2.4 @ 270 A
2 @ 1000 A, 2.4 @ 833 A
Current measurement AC 100.1 Hz to 1 kHz Range 40 A / 400 A / 2000 A; 1400 AC RMS
Resolution 10 mA / 100 mA / 1 A
Accuracy 10 A: 3.5% rdg + 15 digits
10 A: 3.5% rdg + 5 digits
Trigger level for Inrush 0.50 A / 5.0 A / 5 A
Trigger level for Hz filter OFF 2.50 A / 2.5 A / 8 A
Trigger level for Hz filter ON 0.50 A / 2.5 A / 8 A
Frequency measurement Measurement range 5.0 Hz to 1 kHz
Resolution 0.1 Hz (15 Hz to 399.9 Hz); 1 Hz (400 Hz to 1 kHz)
Accuracy – 5.0 Hz to 100 Hz 0.2% + 2 counts
Accuracy – 100.1 Hz to 1 kHz 0.5% + 5 counts
Trigger level Refer to current and voltage tables
1. Add 2% to error spec for CF > 2
General Specifications
Batteries Six 1.5 V AA NEDA 15 A or IEC LR6
Battery life (with typical usage, backlight off) 100 hours
Test leads Rated to 1000 V
Weight .814 kg (1.8 lb)
Jaw size 58 mm (2.28 in)
Dimensions (L x W x D) 300 x 98 x 52 mm (12 x 3.75 x 2 in)
Safety rating IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III
Environmental Specifications
Operating temperature 32°F to +122°F (0°C to +50°C)
Storage temperature -4°F to 140°F (-20°C to +60°C)
Operating humidity 0 to 95% (non-condensing)
Operating altitude 2000 m
Storage altitude 10,000 m
IP rating 42 (indoor use only)
Drop test requirements 1 m
EMI, RFI, EMC FCC part 15, IEC/EN 61326-1:1997 class B
IEC/EN 61326:1997 3V/m, performance criteria B, EN61325
Temperature coefficients Current 0.1% of reading per °C outside 22°C to 24°C
Voltage 0.1% of reading per °C outside 22°C to 24°C

 

SHIPPING

A delivery and handling charge applies to all orders with the exception of back-ordered items.

Unless otherwise required by Buyer, Seller will make transport arrangements as follows:

For deliveries within the metropolitan areas of mainland State capital cities a standard freight charge may be added to invoice; goods

For delivery outside those areas, seller will select the transport to be used and prepay freight for Buyer. Seller will then bill Buyer for freight at Seller's discretion.

Should the Buyer request goods be sent to a Post Office box the Buyer acknowledges this method is the only available and therefore the Seller is not liable for undelivered goods.

Free shipping on orders over $199 incl GST (valid for 1 delivery per order and excludes NT, WA & TAS). If only part of the order is in stock, the customer has the option of paying for a second delivery if they require a partial shipment prior to all goods becoming available. Mektronics Australia reserves the right to charge additional freight in the event of hazardous, bulky or heavy items ordered.

DELIVERY TIME

All quoted delivery or consignment dates are estimates only, given without engagement.

Delay in consignment of any part of an order shall not relieve Buyer of its obligation to accept and pay for the remainder of the order.

Except as provided in paragraph 1.2 of Terms & Conditions, seller will not be liable to pay damages or compensation for any injury or loss sustained by Buyer

a) in the event of a delay in consignment or delivery of goods: or

b) in the event of non delivery.

Goods offered ex-stock by Seller are subject to prior sale.

In the event of any happening beyond Seller's reasonable control in consequence of which Seller cannot effect consignment by the time or times quoted or specified, Seller shall be entitled to consign part only of an order, suspend consignment or extend the time for consignment, for the period during which such cause of delay operates, or may cancel the order, and in the event of such suspension, extension or cancellation, Seller shall not be liable for damages.